UT586+ Digital RCD Tester
The UT586+ is an instrument crafted for verifying the functionality of single-phase and three-phase electrical leakage protection devices. It is equipped with capabilities to measure fault triggering times and the currents that initiate tripping. Adhering to the CAT III 600V safety rating, it finds broad application across residential, educational, power, manufacturing, metallurgical, and chemical sectors.
Product Details
The UT586+ is an instrument crafted for verifying the functionality of single-phase and three-phase electrical leakage protection devices. It is equipped with capabilities to measure fault triggering times and the currents that initiate tripping. Adhering to the CAT III 600V safety rating, it finds broad application across residential, educational, power, manufacturing, metallurgical, and chemical sectors.
Features of UT586+ Digital RCD Tester
Certifications: CE/RoHS
1. RCD trip time/Current test
2. Multiple range & Auto range
3. Phase angle selection
4. Working voltage: 100V~440V
5. Voltage test: 30~480V
6. Over temp. detection
7. Backlight & APO & Low battery
8. CAT III 600V
FAQ
Q1: What is UT586+?
A1: UT586+ is a digital RCD tester, designed to test and verify single-phase and three-phase residual current protection devices. It can measure RCD trip current and trip time.
Q2: What is the safety rating of UT586+?
A2: It has a CAT III 600V safety rating.
Q3: What is the working voltage range and voltage measurement range?
A3: Working voltage: 100V~440V; Voltage test range: 30V~480V.
Q4: Does UT586+ support auto range?
A4: Yes, it supports multiple measuring ranges and auto range function.
Q5: What is the phase angle selection function for?
A5: It supports phase angle selection for RCD testing, to simulate different test conditions.
Q6: Does it have over-temperature protection?
A6: Yes, it is equipped with over temperature detection function to protect the instrument.
Q7: What convenient functions are built-in?
A7: It comes with LCD backlight, auto power off (APO) and low battery indication.
Q8: What certifications does UT586+ have?
A8: It has CE and RoHS certifications.
Q9: What industries can UT586+ be applied to?
A9: It is widely used in residential, educational, power, manufacturing, metallurgical and chemical industries for electrical safety inspection.
Specifications
Specification | |||||
Rate trigger current | Fault trigger time | Accuracy | Accuracy | ||
RCD test function | X1/2 | 10/20/30/100/300/500mA/1000mA | 0~2000mS @ 0°/180° | -10%~0%” | ±0.6%rdg±4dgt |
X1 | 10/20/30/100/300mA | 0~2000mS @ 0°/180° | 0%~+10% | ±0.6%rdg±4dgt | |
500mA/1000mA | 0~200mS @ 0°/180° | 0%~+10% | ±0.6%rdg±4dgt | ||
X2 | 10/20/30/100/200/300/500mA | 0~200mS @ 0°/180° | 0%~+10% | ±0.6%rdg±4dgt | |
X5 | 10/20/30/100/200mA | 0~200mS @ 0°/180° | 0%~+10% | ±0.6%rdg±4dgt | |
AUTO | 10/20/30/100/300/500mA/1000mA | 300ms @ 15 0°/180° | -10%~+10% | ±0.6%rdg±4dgt | |
Manual | 10/20/30/100/300/500mA/1000mA | 300ms @ 0°/180° | -10%~+10% | ±0.6%rdg±4dgt | |
Working voltage | 50/60Hz | 100V~440V | -15%~+10% | ||
Voltage test | Voltage range | 30~480V (Resolution: 1V) | 45~65Hz | ±3%rdg±3dgt | |
Voltage test | L-PE | yes, display the L-PE input voltage; | |||
Frequency | yes, display the L-PE input frequency; | ||||
Wiring check | If there is no wiring, an abnormal power supply, or no electricity flowing, the LCD will display “L-PE” and flash. | ||||
Phase angle selection | You can choose to initiate the test from the positive (0°) or the negative (180°) half-cycle. Press the “0°/180°” button to toggle phase. | ||||
Lock test | With the power disconnected, press and hold the “0°/180°” button to activate the lock test function. Simply connect the test leads correctly to the test points, and the test will run automatically. | ||||
AUTO RAMP test | You can test the trip action current and action time simultaneously. | ||||
RCD test exceeds limit prompt | When the trip action time exceeds the maximum test duration and trips. | ||||
Over-temperature detection | If the internal components of the device become too hot, the LCD will display an over-temperature symbol, and the device will automatically disable RCD testing. | ||||
Backlight | Yes, can be turn on/off | ||||
Low battery indication | yes | ||||
Auto powwer off | After 5 minutes of no operation, it will automatically shut down. | ||||
Working environment | 0℃~40℃ | ||||
Storage environment | -20℃~60℃ | ||||
Power | 8 * 1.5V AA | ||||
Polution level | 2 | ||||
Safety rating | IEC61010-031; IEC61557-1,6; CAT III 600V | ||||
General Features | |||||
Product color | Red + gray | ||||
Product weight | 725g | ||||
Product dimension | 161*117*68mm | ||||
Standard accessories | User manual 1pcs; Test lead 1 set(red/green); Alligator clips 2pcs(red/green); Test probe 2pcs(red/green); 1.5V AA * 8pcs; Test lead to EU plug 1pcs | ||||
Standard package | Carton box: 4pcs | ||||
Package dimension | 585×380×335mm | ||||