Measurement Basics
Measurement Terms Explained
Specifications only make sense when the terms behind them are clear. These are the definitions our engineers use when specifying instruments for industrial testing.
- True RMS
- True root-mean-square measurement: the instrument samples the waveform and calculates its effective value, so readings stay accurate on distorted or non-sinusoidal AC such as inverter, VFD or switch-mode power supply output. Average-responding meters assume a sine wave and read low on these loads.
- Rogowski Coil
- A flexible, air-cored current sensor formed into a closed loop around a conductor. Because there is no iron core to saturate, it measures large or fast-changing AC currents over a wide frequency range, and it is used in clamp meters with flexible current probes.
- Leakage Current
- Current that flows to earth through insulation or a protective conductor instead of the intended circuit. Measured in milliamps with a leakage clamp meter, it indicates insulation ageing, moisture or damage in equipment and distribution systems.
- Insulation Resistance
- The resistance of insulation between conductors, or between a conductor and earth, measured by applying a DC test voltage such as 250 V, 500 V or 1000 V. A falling value points to moisture, contamination or mechanical damage in cables and motors.
- Measurement Category (CAT II / III / IV)
- The IEC 61010 safety classification of where a meter may be connected: CAT II covers socket outlets and portable equipment, CAT III covers distribution boards and fixed installations, and CAT IV covers the service entrance and outdoor supply. The category is always read together with the voltage rating printed on the instrument.